SimReader tools

SimReader’s Tools take care of model file chores that eQUEST and IDF Editor don’t do for you: naming each space’s zone, plenum and system after the space, and putting spaces and systems in name order. Each of these checks the file before saving it and keeps a backup you can restore. Calculators work out the inputs you’d otherwise figure by hand, and Average rates gives each state’s average electricity and natural gas prices.

On this page

Sort spaces and systems

eQUEST and IDF Editor list spaces, zones and HVAC systems in the order they are in the model file, so a long list can be hard to work with. Sort spaces and systems puts them in name order, and you can adjust the order before you save it. It reads eQUEST models (.inp) and EnergyPlus models (.idf).

Sort an eQUEST model

  1. Close the project in eQUEST. eQUEST writes over the model file when it saves a project, so a sort made while it’s open would be lost.
  2. In SimReader, select Tools in the left menu, then Sort spaces and systems.
  3. SimReader fills in the model file that is next to the .SIM file on the Project page. To use another one, select Browse and choose the project’s .inp file.
  4. The page has two sections, Spaces and HVAC systems, each with its own tick boxes and lists. Spaces, within each floor, HVAC systems and Zones, within each system are ticked. Floors keep their order unless you tick it, since they usually go from the bottom to the top.
  5. Compare the New order with the one Now. The names that move are in blue. Conditioned spaces and zones come first, then plenums and unconditioned ones, which are marked in gray. HVAC systems go by kind: DOAS first (a system with 100% outdoor air, or with DOAS in its name), then the main system type (the one that serves the most zones, often a multizone VAV or PIU), the other types, PSZ, and unit heaters; each kind is in name order and is shown in gray next to the system. Systems that serve only plenums or unconditioned zones come last. Names with numbers sort as numbers: Zone 2 comes before Zone 10.
  6. To adjust the order, select a name and use the section’s up and down arrows, or drag it. A name moves only within its own floor or system. A section’s Sort A–Z again puts its lists back in name order and leaves the other section as it is.
  7. Select Save order to save both sections, then reopen the project in eQUEST.

Sort an EnergyPlus model

  1. Close the file in IDF Editor, which writes over it when it saves.
  2. In SimReader, select Tools, then Sort spaces and systems. SimReader fills in the .idf file that is next to the EnergyPlus report on the Project page, or select Browse and choose one.
  3. The page has two sections, Zones and Air loops. Conditioned zones come first, then plenums and unconditioned zones; a zone’s spaces are in name order under it. Air loops go by kind: DOAS first (a loop without a return, or with DOAS in its name), then the kind that serves the most zones (often VAV or PIU), the other kinds, and single-zone loops.
  4. Each zone’s objects follow the zone order is ticked: surfaces, windows, people, lights, equipment, thermostats and zone HVAC are then listed zone by zone, in the zones’ order, so IDF Editor shows them the same way. Untick it to move only the zones.
  5. The zones under each air loop are shown in gray for reference. They follow the zone order, so move a zone in Zones.
  6. Adjust the order as for eQUEST, then select Save order and reopen the file in IDF Editor.

What changes, and what doesn’t

  • Only the order changes. Every line stays as it was.
  • eQUEST: a space moves with its walls, windows and doors, and a system with its zones. eQUEST writes some constructions and materials among a floor’s spaces. When the spaces change order, these go to the top of that floor, in the same order, so each one is still above every wall that uses it.
  • EnergyPlus: objects change order only among objects of the same type, and every type keeps its place in the file. EnergyPlus finds objects by name, so the results don’t change.
  • Before saving, SimReader checks that every component or object is still there, unchanged. If the check fails, nothing is saved.
  • If eQUEST or IDF Editor is running when you select Save order, SimReader asks first.
  • If you go back to the eQUEST wizard later, it rebuilds the model file and the order is lost.

Undo a sort

The order before the last sort is saved next to the model file as name - before sort.inp (or .idf). Select Restore in the tool to put it back.

Rename after spaces

eQUEST’s wizard gives zones, plenums and systems names like “EL1 South Perim Zn (G.S1)”. When you give the spaces real names, the zones, plenums and systems keep the wizard’s. Rename after spaces names them after their space, and changes every place in the model file that refers to them. It works with eQUEST models (.inp).

  1. Close the project in eQUEST. eQUEST writes over the model file when it saves a project, so names saved while it’s open would be lost.
  2. In SimReader, select Tools, then Rename after spaces. SimReader fills in the model file that is next to the .SIM file on the Project page, or select Browse and choose one.
  3. Enter the space names, either in eQUEST beforehand or in the Space column of the table. The table has a row for each space, under its floor.
  4. Each row shows the space’s Zone, Plenum (the plenum space above it), Plenum zone and System, with the name now and the new one. Names that change are in blue.
  5. Check the Naming words. A word of the space name is replaced by each part’s word: with Spc replaced by zn, “Office 101 Spc” gives the zone “Office 101 zn”, the plenum “Office 101 plnm” and the plenum zone “Office 101 plnm zn”. The word matches in any capitals: “Spc”, “spc” and “SPC” all count. A space name without the word gets the part’s word at the end: “Waiting 103” gives “Waiting 103 zn”. The system’s name is the System prefix right before the space name without its word: “101 Spc” gives “s101”, and “Waiting 103” gives “sWaiting 103”. For names like SP-01-01, replace SP with ZONE, PNS and PZONE, with AHU as the system prefix: the system is “AHU-01-01”. SimReader remembers your words.
  6. To use another name, type over it, then press Enter or move to another cell; the names that follow from it, and any name used twice, show then. To go back to the name after the space, clear it. Untick a row to leave its names as they are.
  7. Select Save names, then reopen the project in eQUEST.

Rename on the floor plan

Floor plan shows the spaces floor by floor, as they’re drawn in the model file; Table lists them. Both show the same names, and Save names saves both.

  • Pick a floor with the buttons above the plan. Spaces whose names change are blue, spaces with a name that can’t be used are red, and unconditioned spaces are gray. Plenums aren’t drawn: they sit above their space.
  • Click a space and type its name in the box on it. Enter takes the name and goes to the next space, top to bottom and left to right, then on to the next floor, so a whole floor can be named in one go. Tab and Shift+Tab move between spaces; Esc puts the name back.
  • The panel beside the plan shows the selected space’s zone, plenum, plenum zone and system, the name now and the new one. Type over any of them as in the table.
  • The mouse wheel zooms and dragging moves the plan; Fit shows the whole floor again. A name that doesn’t fit in its space is cut short: point to the space to see it.
  • A space without a shape SimReader can draw is listed under the plan; rename it in the Table.

Which plenum and system are renamed

  • A space’s plenum is the space on the same floor with the same polygon and position, above it. Its zone is the plenum zone.
  • A space’s system is the system its zone is under, when that system serves only this space’s zone and its plenum’s zone.
  • A plenum that covers a whole floor, and a system that serves several spaces, are shown as shared, kept and aren’t renamed.

Before saving

  • New names must be unique in the file and 32 characters at most (eQUEST’s limit), without quote marks. A name that can’t be used is in red; point to it to see why. Save names stays off until it’s fixed.
  • Before saving, SimReader checks that every line is as it was apart from the renamed names, and that every reference to an old name now uses the new one. If the check fails, nothing is saved.
  • Comments in the file aren’t changed.
  • If eQUEST is running when you select Save names, SimReader asks first.

Undo a rename

The names before the last rename are saved next to the model file as name - before rename.inp. Select Restore in the tool to put them back.

Calculators

Calculators work out the values you enter in a model: efficiencies in eQUEST’s terms, fan and pump power, glazing and air leakage inputs, coil loads and dwelling unit lighting. Select Tools, then Calculators, and pick one from the list.

  • Results update as you type. The values that go into the model are in bold, with the eQUEST keyword they go to beside them; Copy puts one on the clipboard the way eQUEST takes it.
  • How it’s worked out shows each step with your numbers. Copy calculation copies the inputs, the steps and the results as text, for your modeling report or a reviewer’s question.
  • Calculators with a baseline and a proposed side have Baseline and Proposed tabs under their title. The tab you pick stays picked for the others.
  • Each calculator remembers your last inputs. Save keeps them in the project’s .ine file, and opening the project brings them back. Example values puts a calculator’s example back.
  • A value outside the usual range gets a note under its box. It’s still used: check it.

The ASHRAE 90.1 edition

Choose the edition once, under Baseline rules above the list: 90.1-2007, 2010, 2013, 2016, or 2019 or 2022. Every calculator with a baseline follows it, and says which edition it’s using.

Baseline fan power and its credits

Tick the pressure drop credits that apply. A ticked credit uses the supply airflow unless you type the airflow through that device in its box. The usual credits are shown; select More credits and deductions for the rest. The list follows the edition you chose.

Many systems at once

System: EIR and HIR (on its Baseline tab) and Fan power can work out many systems together. Dwelling unit lighting does the same with Many rooms, and adds up the rooms into the dwelling unit, where ENERGY STAR’s 0.6 W/ft² check applies.

  1. Select Many systems at the top of the calculator.
  2. In Excel, copy the rows: a name and the values, or the values alone. The table’s headings show which values it takes.
  3. Select Paste rows from Excel. You can also type in the rows; Add row adds one.
  4. Select Copy results, and paste the table back in Excel.

The choices above the table, such as the baseline system and the ticked credits, apply to every row. One system takes you back.

GroupCalculators
Packaged systemsSystem: EIR and HIR. Baseline: the EIR and HIR with the supply fan taken out, from the edition’s table by system and capacity (90.1-2016 and later) or from a rating you enter; eQUEST’s value is there for when the baseline’s doesn’t apply. Proposed: a packaged unit’s EIR or HIR with the fan power taken out of its rating (an EER, SEER, SEER2, EER2 or IEER; a COP47, HSPF or HSPF2), a VRF system’s indoor fan and outdoor unit EIR, or a rating conversion (SEER, IEER, EER2, SEER2, HSPF2, ISMRE2, HSPF, COP47) · Furnace HIR: the baseline gas furnace’s by the edition; a proposed furnace’s from its AFUE, Et or Ec
Chilled and hot water plantChiller. Baseline: the number and type of chillers from the building’s peak cooling load, and each one’s efficiency and EIR by the edition. Proposed: the EIR from its kW/ton or COP · Cooling tower. Baseline: the approach, EIR, fan control and leaving water temperature by the edition. Proposed: the fan efficiency, checked against the edition’s minimum, and the EIR · Boiler HIR: the baseline gas boilers’ minimum efficiency for each size by the edition; a proposed boiler’s from its AFUE, Et or Ec · Pump power: the HEAD, MECH-EFF and MOTOR-EFF to enter in eQUEST per pump. For the baseline from 90.1’s W/GPM (chilled water as a primary and a secondary pump, with their capacity control) or a W/GPM; for a proposed pump from its schedule (head with efficiencies or BHP) or its power, with BHP, kW and W/GPM to check (the flow per pump is needed only for the BHP and kW there)
FansFan power: the baseline’s, with pressure drop credits and the split into supply, return and exhaust, and a proposed fan’s · Garage ventilation: demand control: the baseline at 0.75 CFM/ft² and 0.3 W/CFM on at all hours (where an exception to 90.1’s garage rule lets it run without the controls), the proposed fans’ energy from their design kW and a 24-hour schedule for weekdays, Saturdays and Sundays (drag it on the chart or paste it from Excel; Save as .inp writes eQUEST’s day, week and annual schedules to import), the 0.05 CFM/ft² minimum and the 75% savings limit. It follows the edition: LEED 2009 and v4 accept the method; from 90.1-2013 the rating authority must approve the baseline; 90.1-2022’s garage rule exempts only a single section of 5 hp or less
Service water heatingWater heater. Baseline: the gas or electric heater’s HIR or EIR and tank UA from the edition’s minimum efficiency for its type and size, sized as the proposed heater (2007 and 2010: the proposed heater’s type; from 2013: storage, with its own tank volume when the proposed heater is tankless). Proposed: the HIR, or an electric heater’s EIR, from a UEF, EF or thermal efficiency, an electric heater’s capacity, a tank’s UA from its standby loss
EnvelopeGlazing for DOE-2: SHADING-COEF and GLASS-CONDUCT for the baseline window from its assembly U-factor and SHGC, and for the proposed window from its center-of-glass and frame values, as one whole window (the frame isn’t modeled; FRAME-CONDUCT is shown for information); the outside air film comes off by DOE-2’s own table, for the wind speed of the rating · Air leakage: AIR-CHANGES/HR (INF-METHOD = AIR-CHANGE, which eQUEST corrects for wind each hour) from the leakage at 75 Pa, the envelope area from its parts and the conditioned volume. Baseline: the edition’s rate (0.4 CFM/ft² in 2013 and 2016, 1.0 from 2019). Proposed: measured, with a verified air barrier (0.6 in 2019, 0.45 in 2022), entered, or the baseline’s. The rates per floor and wall area are shown for information
LightingDwelling unit lighting: the area a room’s fixtures light, and its baseline and proposed W/ft²; Many rooms adds up a dwelling unit and checks its 0.6 W/ft²
Sizing checksCoil load: a cooling coil’s sensible and total load from airflow and entering and leaving air, with tons, latent load and sensible heat ratio, or a heating coil’s load (it adds no moisture), and the water flow, to check whether a design’s coil is oversized or undersized · Supply air ΔT or airflow, at your altitude, to check a baseline system’s airflow against the baseline rules (a 20 °F supply-to-room difference for most systems)

The coil load works out humidity and enthalpy from dry-bulb and wet-bulb at your altitude, so you don’t need a psychrometric chart. The air factors (1.08 and 4.45) are adjusted for altitude too.

Average rates

Average rates gives each state’s average electricity and natural gas prices from the U.S. Energy Information Administration (EIA), for a model’s utility rates when you don’t have the actual ones. LEED accepts the EIA’s state averages. Select Tools, then Average rates.

  1. Pick the state, and Commercial or Residential.
  2. The electricity rate is in $/kWh and the natural gas rate in $/therm, as eQUEST and SimReader’s virtual rates take them. Under each is the EIA’s own figure (cents/kWh, or $/Mcf with the heat content used to give therms) and its year.
  3. Copy puts a rate on the clipboard. All states lists every state’s rates; select a row to pick its state.

The rates are each state’s latest year the EIA has published. Where it hasn’t published a state’s latest year of natural gas prices, the year before is used and shown. SimReader reads the rates from InverseHub each time it starts, so you get new ones as soon as they’re updated. Without the internet, it uses the rates it read last time and says when it read them.

To use the averages in a model’s results, select Use state averages under Utility Rates on the Results page. See The Results page.